Standard Historical Last Updated: Jan 15, 2019 Track Document
ASTM F2675/F2675M-13

Standard Test Method for Determining Arc Ratings of Hand Protective Products Developed and Used for Electrical Arc Flash Protection

Standard Test Method for Determining Arc Ratings of Hand Protective Products Developed and Used for Electrical Arc Flash Protection F2675_F2675M-13 ASTM|F2675_F2675M-13|en-US Standard Test Method for Determining Arc Ratings of Hand Protective Products Developed and Used for Electrical Arc Flash Protection Standard new BOS Vol. 10.03 Committee F18
$ 83.00 In stock

Significance and Use

5.1 This test method is intended for the determination of the arc rating of a hand protective product material, or a combination of hand protective product materials.

5.1.1 Because of the variability of the arc exposure, different heat transmission values are observed at individual sensors. Evaluate the results of each sensor in accordance with Section 12.

5.2 This test method maintains the specimen in a static, vertical position and does not involve movement except that resulting from the exposure.

5.3 This test method specifies a standard set of exposure conditions. Different exposure conditions have the potential to produce different results. In addition to the standard set of exposure conditions, other conditions are allowed and shall be documented in the reporting of the testing results.

Scope

1.1 This test method is used to determine the arc rating of hand protective products in the form of gloves, glove materials, glove material systems, or other protective products designed to fit on the hand and specifically intended for electric arc flash protection use as protective accessories for workers exposed to electric arc heat flux values from 84 to 25,120 kW/m2 [2 to 600 cal/cm2s].

1.2 This test method will determine the arc rating of hand protective products made of materials which meet the following requirements for flame resistance: less than 150 mm [6 in.] char length, less than 2 s afterflame and no melt and drip when tested in accordance with Test Method D6413 or receive a reported 50 % probability of ignition of a material or flammable underlayer (see definition of ignition50) by this method.

1.2.1 It is the intent of this test method to be used for hand protective products which are flame resistant or which have an adequate flame resistance for the required hazard (see 1.2). Non flame resistant hand protective products may be used as under layers in multiple-layer systems or tested for ignition probability.

1.2.2 It is not the intent of this test method to be used for glove materials, which have been tested by Test Method F1959/F1959M as flat panels of material then sewn into hand protective products. Materials for hand protective products, which are not normally produced in flat panels or which display shrinkage making the material unacceptable to test on panels, shall be tested using this standard.

1.2.3 Rubber insulating gloves meeting Specification D120 and leather protectors meeting Specification F696 are not covered by this test method and are specifically excluded from its Scope.

1.2.4 Hand protective products tested by this method are new and ratings received by this method may be reduced or eliminated by hydrocarbon loading (gasoline, diesel fuel, transformer oil, etc.), sweat, dirt, grease, or other contaminants. The end user takes responsibility for use of hand protective products tested by this method when contaminated in such a manner which could reduce or eliminate the arc rating of the hand protective products.

1.2.5 Gloves tested by this method provide no protection from electric shock. Insulated gloves for protection from electric shock are addressed under other standards including ASTM D120. This test method is designed to provide information for gloves used for electric arc protection only. This test method is not suitable for determining electrical protective properties of hand protective products.

1.3 This test method is used to measure and describe the properties of hand protective products in response to convective and radiant energy generated by an electric arc under controlled laboratory conditions.

1.4 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard.

1.5 This test method does not apply to electrical contact or electrical shock hazards.

1.6 This standard shall not be used to describe or appraise the fire hazard or fire risk of materials, products, or assemblies under actual fire conditions. However, results of this test may be used as elements of a fire assessment that takes into account all of the factors, which are pertinent to an assessment of the fire hazard of a particular end use.

1.7 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. For specific precautions, see Section 7.

Price:
Contact Sales
Related
Reprints and Permissions
Reprints and copyright permissions can be requested through the
Copyright Clearance Center
Details
Book of Standards Volume: 10.03
Developed by Subcommittee: F18.65
Pages: 13
DOI: 10.1520/F2675_F2675M-13
ICS Code: 13.340.10