ASTM E3225-20

Standard Practice for Performing a Liquid Test of Spill Prevention Equipment and Containment Sumps Used for Interstitial Monitoring of Piping by Visual Examination

Standard Practice for Performing a Liquid Test of Spill Prevention Equipment and Containment Sumps Used for Interstitial Monitoring of Piping by Visual Examination E3225-20 ASTM|E3225-20|en-US Standard Practice for Performing a Liquid Test of Spill Prevention Equipment and Containment Sumps Used for Interstitial Monitoring of Piping by Visual Examination Standard new BOS Vol. 11.05 Committee E50
$ 75.00 In stock
ASTM International

Significance and Use

5.1 Periodic testing of spill prevention equipment and containment sumps used for interstitial monitoring of piping is required by US EPA regulation § 40 CFR §280.35.

5.2 The spill prevention equipment and containment sumps used for interstitial monitoring of piping must be tested at least once every three years to ensure the equipment is liquid tight by using vacuum, pressure, or liquid testing according to § 40 CFR §280.35. Under this practice, an annual test is required.

5.3 The phrase liquid tight is an ambiguous expression with the acceptable leak rate dependent upon the nature of the liquid and the purpose of the evaluated material. This practice defines liquid tight.

5.3.1 There is no minimum containment capacity or leak rate criteria for spill prevention equipment or containment sumps used for interstitial monitoring of piping.

5.4 Spill prevention equipment and containment sumps are designed to contain a regulated substance that is released from the primary fuel path of a UST system including leaks that occur when the delivery hose is disconnected from the fill pipe, until the regulated substance is detected and removed. There is no established maximum leak rate, capacity requirement or holding time.

5.5 Spill prevention equipment and containment sumps must be properly installed pursuant to § 40 CFR §280.20 in accordance with a code of practice developed by a nationally recognized association or independent testing laboratory and in accordance with the manufacturer's instructions. Properly installed spill prevention equipment and containment sumps will perform as designed unless one or more components have become compromised. Indications of component compromise that could impact the capability of a sump to remain liquid tight are visually observable.

5.6 This practice is used to perform a liquid test of sumps to determine if the sumps are liquid tight, capable of containing a regulated substance leaked from the primary fuel path of the UST system until the regulated substance is detected and removed.

5.7 Liquid testing by visual examination is the process of using the naked eye, alone or in conjunction with various aids such as portable lighting, camera, or mirrors, as the sensing mechanism from which a determination is made about the condition of the sump being inspected.

5.8 This practice is only applicable to spill prevention equipment and containment sumps after installation testing is complete. Properly installed spill prevention equipment and containment sumps will remain liquid tight unless one or more components become compromised.

5.9 The periodic operation and maintenance walkthrough inspections required by §40 CFR §280.36 will not comply with this practice unless conducted by a professional inspector and all requirements of Section 7 are addressed.

5.10 This practice is not applicable where components are not observable.

5.11 This practice does not supersede requirements developed by the manufacturer of items tested, if any requirements exist.

Scope

1.1 Spill prevention equipment, and containment sumps are tested periodically to ensure the equipment is liquid tight by using vacuum, pressure, or liquid testing pursuant to United States of America federal regulations found in § 40 CFR 280.35.

1.2 This practice provides a liquid test by visual examination conducted by a professional inspector to determine if the spill prevention equipment and containment sumps are liquid tight.

1.3 The user is expected to have knowledge of UST installation procedures and UST operational, maintenance and testing requirements of § 40 CFR 280 et seq, related to the tasks performed.

1.4 Section 6 provides the minimum qualifications and educational requirements of a professional inspector. The authority having jurisdiction may have additional certification requirements.

1.5 This practice offers a set of instructions for performing one or more specific operations. This document cannot replace education or experience and should be used in conjunction with professional judgment. Not all aspects of this practice may be applicable in all circumstances. This ASTM standard is not intended to represent or replace the standard of care by which the adequacy of a given professional service must be judged, nor should this document be applied without consideration of a project’s many unique aspects. The word “Standard” in the title means only that the document has been approved through the ASTM consensus process.

1.6 The values stated in SI units are to be regarded as standard. No other units of measurement are included in this standard.

1.7 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. Hazards known to this practice are identified in Section 8.

1.8 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.