    STP1596

    Auto Ignition Temperature Test Chamber Fire Investigation

    Published: 2016


      Format Pages Price  
    PDF (2.5M) 12 $25   ADD TO CART
    Complete Source PDF (55M) 439 $128   ADD TO CART

    Cite this document

    X Add email address send
    X
      .RIS For RefWorks, EndNote, ProCite, Reference Manager, Zoteo, and many others.   .DOCX For Microsoft Word


    Abstract

    During routine auto ignition temperature (AIT) testing of a solvent at the NASA White Sands Test Facility (WSTF), a fire breached the test system. The sample being tested was 99 % dodecane (C12). It was exposed to a test atmosphere of 15.7 MPa gas, meeting aviator’s breathing oxygen (ABO) specifications (≥99.5 % O2). During testing, a metal fire occurred, resulting in multiple breaches of the test system. During the event, the chamber pressure transducer mechanically burst, indicating a pressure increase of at least 159 MPa/s. This fire represented the first AIT system breach in 30 years of testing at WSTF. An investigation was undertaken to determine the cause of the breach and to propose countermeasures to prevent future mishaps. A proposed ignition scenario is presented along with an approach for preventing future incidents.

    Keywords:

    G72/G72M-09, autogenous ignition temperature, failure analysis, fire investigation