ASTM D2220-02(2007)e1

    Standard Specification for Poly(Vinyl Chloride) Insulation for Wire and Cable, 75 °C Operation


      Format Pages Price  
    PDF 2 $52.00   ADD TO CART


    1. Scope

    1.1 This specification covers a thermoplastic insulation of poly(vinyl chloride) or the copolymer of vinyl chloride and vinyl acetate.

    1.2 This insulation is recommended for use in power and control circuits at temperatures not higher than 75 °C. At a thickness of 15 mils (0.38 mm), application is limited to voltage ratings below 300 V, and to dry locations. At a thickness of 30 mils, the application range is widened to dry or wet applications, and to a voltage rating of 600 V.

    1.3 Whenever two sets of values are presented, in different units, the values in the first set are the standard, while those in parentheses are for information only.

    1.4 In many instances the insulation material cannot be tested unless it has been formed around a conductor or cable. Therefore, tests are done on insulated wire or cable in this specification solely to determine the relevant property of the insulation material and not to test the conductor or completed cable.


    2. Referenced Documents (purchase separately) The documents listed below are referenced within the subject standard but are not provided as part of the standard.

    ASTM Standards

    D1711 Terminology Relating to Electrical Insulation

    D2633 Test Methods for Thermoplastic Insulations and Jackets for Wire and Cable

    G153 Practice for Operating Enclosed Carbon Arc Light Apparatus for Exposure of Nonmetallic Materials

    G155 Practice for Operating Xenon Arc Light Apparatus for Exposure of Non-Metallic Materials


    ICS Code

    ICS Number Code 29.035.20 (Plastic and rubber insulating materials)

    Referencing This Standard
    Link Here
    Link to Active (This link will always route to the current Active version of the standard.)

    DOI: 10.1520/D2220-02R07E01