Standard Historical Last Updated: Apr 29, 2013 Track Document
ASTM D149-09

Standard Test Method for Dielectric Breakdown Voltage and Dielectric Strength of Solid Electrical Insulating Materials at Commercial Power Frequencies

Standard Test Method for Dielectric Breakdown Voltage and Dielectric Strength of Solid Electrical Insulating Materials at Commercial Power Frequencies D0149-09 ASTM|D0149-09|en-US Standard Test Method for Dielectric Breakdown Voltage and Dielectric Strength of Solid Electrical Insulating Materials at Commercial Power Frequencies Standard new BOS Vol. 10.01 Committee D09
$ 83.00 In stock

Significance and Use

The dielectric strength of an electrical insulating material is a property of interest for any application where an electrical field will be present. In many cases the dielectric strength of a material will be the determining factor in the design of the apparatus in which it is to be used.

Tests made as specified herein are suitable for use to provide part of the information needed for determining suitability of a material for a given application; and also, for detecting changes or deviations from normal characteristics resulting from processing variables, aging conditions, or other manufacturing or environmental situations. This test method is useful for process control, acceptance or research testing.

Results obtained by this test method can seldom be used directly to determine the dielectric behavior of a material in an actual application. In most cases it is necessary that these results be evaluated by comparison with results obtained from other functional tests or from tests on other materials, or both, in order to estimate their significance for a particular material.

Three methods for voltage application are specified in Section 12: Method A, Short-Time Test; Method B, Step-by-Step Test; and Method C, Slow Rate-of-Rise Test. Method A is the most commonly-used test for quality-control tests. However, the longer-time tests, Methods B and C, which usually will give lower test results, will potentially give more meaningful results when different materials are being compared with each other. If a test set with motor-driven voltage control is available, the slow rate-of-rise test is simpler and preferable to the step-by-step test. The results obtained from Methods B and C are comparable to each other.

Documents specifying the use of this test method shall also specify:

Method of voltage application,

Voltage rate-of-rise, if slow rate-of-rise method is specified,

Specimen selection, preparation, and conditioning,

Surrounding medium and temperature during test,

Electrodes,

Wherever possible, the failure criterion of the current-sensing element, and

Any desired deviations from the recommended procedures as given.

If any of the requirements listed in 5.5 are missing from the specifying document, then the recommendations for the several variables shall be followed.

Unless the items listed in 5.5 are specified, tests made with such inadequate reference to this test method are not in conformance with this test method. If the items listed in 5.5 are not closely controlled during the test, it is possible that the precisions stated in 15.2 and 15.3 will not be obtained.

Variations in the failure criteria (current setting and response time) of the current sensing element significantly affect the test results.

Appendix X1. contains a more complete discussion of the significance of dielectric strength tests.

Scope

1.1 This test method covers procedures for the determination of dielectric strength of solid insulating materials at commercial power frequencies, under specified conditions. ,

1.2 Unless otherwise specified, the tests shall be made at 60 Hz. However, this test method is suitable for use at any frequency from 25 to 800 Hz. At frequencies above 800 Hz, dielectric heating is a potential problem.

1.3 This test method is intended to be used in conjunction with any ASTM standard or other document that refers to this test method. References to this document need to specify the particular options to be used (see 5.5).

1.4 It is suitable for use at various temperatures, and in any suitable gaseous or liquid surrounding medium.

1.5 This test method is not intended for measuring the dielectric strength of materials that are fluid under the conditions of test.

1.6 This test method is not intended for use in determining intrinsic dielectric strength, direct-voltage dielectric strength, or thermal failure under electrical stress (see Test Method D3151).

1.7 This test method is most commonly used to determine the dielectric breakdown voltage through the thickness of a test specimen (puncture). It is also suitable for use to determine dielectric breakdown voltage along the interface between a solid specimen and a gaseous or liquid surrounding medium (flashover). With the addition of instructions modifying Section 12, this test method is also suitable for use for proof testing.

1.8 This test method is similar to IEC Publication 243-1. All procedures in this method are included in IEC 243-1. Differences between this method and IEC 243-1 are largely editorial.

1.9 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. Specific hazard statements are given in Section 7. Also see 6.4.1.

Price:
Contact Sales
Related
Reprints and Permissions
Reprints and copyright permissions can be requested through the
Copyright Clearance Center
Details
Book of Standards Volume: 10.01
Developed by Subcommittee: D09.12
Pages: 13
DOI: 10.1520/D0149-09