Abstract

This specification covers mineral fiber (rock or slag) insulating and finishing cement shipped in dry-mix form, including hydraulic-setting binder, which, when mixed with water and applied in accordance with the manufacturer's directions, affords a smooth surface as a final finish for heated surfaces for specific applications. The actual temperature limit shall be agreed upon between the purchaser and the manufacturer. Specimens shall be sampled, prepared, tested, and conform accordingly to the following properties: dry covering capacity, volume change upon drying, compressive strength, linear shrinkage, apparent thermal conductivity, maximum use temperature, and non-combustibility.

Scope

1.1 This specification covers mineral fiber (rock or slag) insulating and finishing cement shipped in dry-mix form, including hydraulic-setting binder, which, when mixed with water and applied in accordance with the manufacturer's directions, affords a smooth surface as a final finish for heated surfaces up to 1200 °F (649 °C) for specific applications. The actual temperature limit shall be agreed upon between the purchaser and the manufacturer.

Note 1Precautionary measures should be taken with this material as with other hydraulic-setting mixtures. This material should be used within the time period recommended by the manufacturer.

1.2 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.

1.3 The following safety hazards caveat pertains only to the test method (Section 10) described in this specification: This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

1.4 When the installation or use of thermal insulation materials, accessories, and systems pose safety or health problems, the manufacturer shall provide the user with appropriate current information regarding any known problems associated with the recommended use of the company's products and shall also recommend protective measures to be employed in their safe utilization. The user shall establish appropriate safety and health practices and determine the applicability of regulatory requirements prior to use.