ASTM E1966 - 07(2011)

    Standard Test Method for Fire-Resistive Joint Systems

    Active Standard ASTM E1966 | Developed by Subcommittee: E05.11

    Book of Standards Volume: 04.07


      Format Pages Price  
    PDF 16 $49.00   ADD TO CART
    Hardcopy (shipping and handling) 16 $49.00   ADD TO CART


    Significance and Use

    This test method evaluates, under the specified test conditions: (1) the ability of a fire resistive joint system to undergo movement without reducing the fire rating of the adjacent fire separating elements and (2) the duration for which test specimens will contain a fire and retain their integrity during a predetermined test exposure.

    This test method provides for the following measurements and evaluations where applicable:

    Capability of the joint system to movement cycle.

    Loadbearing capacity of the joint system.

    Ability of the joint system to prohibit the passage of flames and hot gases.

    Transmission of heat through the joint system.

    Ability of the joint system, that is an extension of a wall, to resist the passage of water during a hose stream test.

    This test method does not provide the following:

    Evaluation of the degree by which the joint system contributes to the fire hazard by generation of smoke, toxic gases, or other products of combustion.

    Measurement of the degree of control or limitation of the passage of smoke or products of combustion through the joint system.

    Measurement of flame spread over the surface of the joint system.

    Note 1—The information in 5.3.1-5.3.3 may be determined by other suitable fire test methods. For example, 5.3.3 may be determined by Test Method E84.

    Evaluation of joints formed by the rated or non-rated exterior walls and the floors of the building.

    In this procedure, the test specimens are subjected to one or more specific sets of laboratory test conditions. When different test conditions are substituted or the end-use conditions are changed, it is not always possible by, or from, this test method to predict changes to the characteristics measured. Therefore, the results are valid only for the exposure conditions described in this test method.

    1. Scope

    1.1 This fire-test-response test method measures the performance of joint systems designed to be used with fire rated floors and walls during a fire endurance test exposure. The fire endurance test end point is the period of time elapsing before the first performance criteria is reached when the joint system is subjected to one of two time-temperature fire exposures.

    1.2 The fire exposure conditions used are either those specified by Test Method E119 for testing assemblies to standard time-temperature exposures or Test Method E1529 for testing assemblies to rapid-temperature rise fires.

    1.3 This test method specifies the heating conditions, methods of test, and criteria for the evaluation of the ability of a joint system to maintain the fire resistance where hourly rated fire-separating elements meet.

    1.4 Test results establish the performance of joint systems during the fire-exposure period and shall not be construed as having determined the joint systems suitability for use after that exposure.

    1.5 This test method does not provide quantitative information about the joint system relative to the rate of leakage of smoke or gases or both. However, it requires that such phenomena be noted and reported when describing the general behavior of joint systems during the fire endurance test but is not part of the conditions of compliance.

    1.6 Potentially important factors and fire characteristics not addressed by this test method include, but are not limited to:

    1.6.1 The performance of the fire-resistive joint system constructed with components other than those tested.

    1.6.2 The cyclic movement capabilities of joint systems other than the cycling conditions tested.

    1.7 The values stated in inch-pound units are to be regarded as the standard. The SI values given in parentheses are for information only.

    1.8 The text of this standard references notes and footnotes which provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the standard.

    1.9 This standard is used to measure and describe the response of materials, products, or assemblies to heat and flame under controlled conditions, but does not by itself incorporate all factors required for fire hazard or fire risk assessment of the materials, products, or assemblies under actual fire conditions.

    1.10 Fire testing is inherently hazardous. Adequate safeguards for personnel and property shall be employed in conducting these tests.

    1.11 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.


    2. Referenced Documents (purchase separately) The documents listed below are referenced within the subject standard but are not provided as part of the standard.

    ASTM Standards

    E84 Test Method for Surface Burning Characteristics of Building Materials

    E119 Test Methods for Fire Tests of Building Construction and Materials

    E176 Terminology of Fire Standards

    E631 Terminology of Building Constructions

    E1529 Test Methods for Determining Effects of Large Hydrocarbon Pool Fires on Structural Members and Assemblies

    E2226 Practice for Application of Hose Stream

    E2307 Test Method for Determining Fire Resistance of Perimeter Fire Barriers Using Intermediate-Scale, Multi-story Test Apparatus


    ICS Code

    ICS Number Code 91.080.40 (Concrete structures)

    UNSPSC Code

    UNSPSC Code 46190000(Fire protection)


    DOI: 10.1520/E1966-07R11

    ASTM International is a member of CrossRef.