Volume 9, Issue 3 (September 1987)

    Failure Analysis of Brittle Fracture in Nonceramic Insulators

    CODEN: CTROAD

      Format Pages Price  
    PDF 6 $25   ADD TO CART


    Abstract

    Time dependent transverse cracking of the glass reinforced polymer (GRP) core rod in nonceramic insulators (NCI) under low mechanical loads, commonly referred to as brittle fracture, has been investigated. Tension tests were performed on GRP core rods with E glass, ECR glass as well as epoxy and polyester matrices using nitric and oxalic acid environments in order to obtain the relationship between applied stress and the time to rupture. While both E glass and ECR glass remain prone to brittle fracture, ECR has a substantially superior resistance to stress corrosion cracking than E glass. Scanning electron microscopy of fracture surfaces has produced a quantitative relationship between the stress history and the fracture mirror size on the fibers. Results of an epoxy cone insulator end fitting are presented, and the mechanism of brittle fracture is discussed.


    Author Information:

    Akhtar, A
    Metallurgical research supervisor and material research engineer, British Columbia Hydro and Power Authority Research and Development, Surrey, British Columbia

    Wong, JY
    Metallurgical research supervisor and material research engineer, British Columbia Hydro and Power Authority Research and Development, Surrey, British Columbia


    Stock #: CTR10248J

    ISSN: 0884-6804

    DOI: 10.1520/CTR10248J

    ASTM International is a member of CrossRef.

    Author
    Title Failure Analysis of Brittle Fracture in Nonceramic Insulators
    Symposium , 0000-00-00