ASTM WK41395

    Work Item: ASTM WK41395 - Revision of C1063 - 12c Standard Specification for Installation of Lathing and Furring to Receive Interior and Exterior Portland Cement-Based Plaster

    (What is a Work Item?)

    Active Standard: C1063 - 14a

    Developed by Subcommittee: C11.03 | Committee C11 | Contact Staff Manager



    1. Rationale

    Concerning changes to 7.10.2.1 At the task group meeting the consensus of the group requested that we submit a ballot change to bring the attachment distances in compliance with the IRC and the IBC. Concerning changes to 7.10.1.2The spacing of framing members for the type and weight of metal plaster base used shall conform to the requirements of Table 3. Metal plaster bases shall be attached to framing member at not more than 7 in (178 mm) 6 in (152 mm) on center, along framing members except for 3/8-in (9.5 mm) rib metal lath that shall be attached at each rib. Attachment penetrations between the framing members shall be avoided (see A1.1). Rationale:At the task group meeting the consensus of the group requested that we submit a ballot change to bring the attachment distances in compliance with the IRC and the IBC.


    Keywords

    ceiling; expansion control joints; lath; plaster; screed; suspended ceiling; walls;