ASTM WK29570

    Revision of E648 - 10 Standard Test Method for Critical Radiant Flux of Floor-Covering Systems Using a Radiant Heat Energy Source

    (What is a Work Item?)

    Active Standard: E648 - 14c

    Developed by Subcommittee: E05.22 | Committee E05 | Contact Staff Manager



    WK29570

    1. Rationale

    Section 6.6 is unclear. A user could interpret it to mean that the air flow rate through the stack should be measured with the radiant panel ignited, which is not the intent. (A hot wire anemometer would not be accurate in that case and would likely be destroyed by the heat). The proposed new wording makes it clear that the flow rate should be measured before igniting the panel. Also, the current section 6.6 discusses the construction of the exhaust duct and measuring the flow rate. The proposed new wording places the sentence about measuring the flow rate into a subsection, new section 6.6.1.


    Keywords

    critical radiant flux; fire; floor-covering systems; radiant panel; Horizontally-mounted floor-covering systems; Radiant heat exposure/testing; Simulated concrete structural floor; Critical radiant flux; Emittance; Fire testing--floors/flooring materials; Flaming ignition; Flammability--floors/flooring systems; Flooring/floor covering systems; Graded radiant heat energy; Heating tests--building products;