Standard Historical Last Updated: Dec 31, 2010 Track Document
ASTM D6760-02

Standard Test Method for Integrity Testing of Concrete Deep Foundations by Ultrasonic Crosshole Testing

Standard Test Method for Integrity Testing of Concrete Deep Foundations by Ultrasonic Crosshole Testing D6760-02 ASTM|D6760-02|en-US Standard Test Method for Integrity Testing of Concrete Deep Foundations by Ultrasonic Crosshole Testing Standard new BOS Vol. 04.09 Committee D18
$ 75.00 In stock

Significance and Use

This method uses data from ultrasonic probes lowered into parallel access ducts in the pile or structure to assess the homogeneity and integrity of concrete between the probes. The data are used to confirm adequate concrete quality or identify zones of poor quality. If defects are detected, then further investigations should be made by excavation or coring the concrete as appropriate, or by other testing such as Test Method D 1143, D 4945 or D 5882, and measures taken to remediate the structure if a defect is confirmed.

Note 1—The quality of the result produced by this standard is dependent on the competence of the personnel performing it, and the suitability of the equipment and facilities used. Agencies that meet the criteria of Practice D 3740 are generally considered capable of competent and objective testing and inspection. Users of this standard are cautioned that compliance with Practice D 3740 does not in itself assure reliable results. Reliable results depend on many factors; Practice D 3740 provides a means of evaluating some of those factors.

Scope

1.1 This test method covers procedures for checking the homogeneity and integrity of concrete in a deep foundation such as bored piles, drilled shafts, concrete piles or augercast piles. This method can also be extended to diaphragm walls, barrettes, dams etc. The test measures the propagation time and relative energy of an ultrasonic pulse between parallel access ducts installed in the pile or structure. This method is most applicable when performed between tubes that are installed during pile construction.

1.2 Similar techniques with different excitation sources or single access ducts, or both, exist, but these techniques are outside the scope of this test method.

1.3 All observed and calculated values shall conform to the guidelines for significant digits and rounding established in Practice D 6026.

1.3.1 The method used to specify how data are collected, calculated, or recorded in this standard is not directly related to the accuracy to which data can be applied in design or other uses, or both. How one applies the results obtained using this standard is beyond its scope.

1.4 LimitationsProper installation of the access ducts is essential for effective testing and interpretation. The method does not give the exact type of defect (for example, inclusion, honeycombing, lack of cement particles, etc.) but rather only that a defect exists. The method is limited primarily to testing the concrete between the access ducts and thus gives little information about the concrete outside the reinforcement cage to which the access ducts are attached when the tubes are attached to the inside of the reinforcement cage.

1.5 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

Price:
Contact Sales
Related
Reprints and Permissions
Reprints and copyright permissions can be requested through the
Copyright Clearance Center
Details
Book of Standards Volume: 04.09
Developed by Subcommittee: D18.11
Pages: 6
DOI: 10.1520/D6760-02
ICS Code: 91.080.40